IEC Elettriku | 75 | 150 | 275 | 320 | ||
Vultaġġ AC nominali (50/60Hz) | Uc/Un | 60V | 120V | 230V | 230V | |
Vultaġġ Operattiv Kontinwu Massimu (AC) | (LN) | Uc | 75V | 150V | 270V | 320V |
(N-PE) | Uc | 255V | ||||
Kurrent ta' Skarigu Nominali (8/20μs) | (LN)/(N-PE) | In | 20 kA/25kA | |||
Kurrent Massimu ta' Skarigu (8/20μs) | (LN)/(N-PE) | Imax | 50 kA/50 kA | |||
Kurrent ta' Kwittanza ta' Impuls (10/350μs) | (LN)/(N-PE) | Iimp | 12.5kA/25kA | |||
Enerġija Speċifika | (LN)/(N-PE) | W/R | 39 kJ/Ω / 156 kJ/Ω | |||
Ħlas | (LN)/(N-PE) | Q | 6.25 As/12.5As | |||
Livell ta' Protezzjoni tal-Vultaġġ | (LN)/(N-PE) | Up | 0.7kV/1.5 kV | 1.0kV/1.5 kV | 1.5 kV/1.5 kV | 1. 6kV/1.5 kV |
(N-PE) | Jekk jien | 100 ARMI | ||||
Ħin ta' Rispons | (LN)/(N-PE) | tA | <25ns/<100 ns | |||
Fjus ta' Back-Up (massimu) | 315A/250A gG | |||||
Klassifikazzjoni tal-kurrent ta' ċirkwit qasir (AC) | (LN) | ISCCR | 25kA/50kA | |||
TOV jiflaħ 5s | (LN) | UT | 114V | 180V | 335V | 335V |
TOV 120min | (LN) | UT | 114V | 230V | 440V | 440V |
mod | Jiflaħ | Safe Fail | Safe Fail | Safe Fail | ||
TOV jiflaħ 200ms | (N-PE) | UT | 1200V | |||
UL Elettriku | ||||||
Vultaġġ Operattiv Kontinwu Massimu (AC) | MCOV | 75V/255V | 150V/255V | 275V/255V | 320V/255V | |
Klassifikazzjoni tal-Protezzjoni tal-Vultaġġ | VPR | 330V/1200V | 600V/1200V | 900V/1200V | 1200V/1200V | |
Kurrent ta' Skarigu Nominali (8/20μs) | In | 20kA/20kA | 20kA/20kA | 20kA/20kA | 20kA/20kA | |
Klassifikazzjoni tal-kurrent ta' ċirkwit qasir (AC) | SCCR | 100kA | 200kA | 150kA | 150kA |